Control line/communication line coupling network, meeting IEC/EN 61000-4-5 and GB/T 17626.5
◆ Coupling pulse peak value: maximum ±7.0kV
◆ Coupling waveform: 1.2/50μs and 10/700μs
◆ Coupling parameters:
1×40Ω + 0.5μF / GAS / ABDs (IEC 61000-4-5 Ed3.0 Figure 9)
4×40Ω, 4×80Ω, 4×160Ω (IEC 61000-4-5 Ed3.0 Figure 10)
4×25Ω (IEC 61000-4-5 Ed3.0 Appendix A Figure 4)
◆ Rated input voltage: 250Vac, 300Vdc
◆ Maximum number of coupling lines: 4
◆ Input/output port: banana socket